7116 Beatty Dr Mission, BC V2V 6B4 Canada Northfire 42 42-dvt40n Direct Vent Gas Fireplace For use with natural gas or propane* Installer: Please
Northfire 42 10 INSTALLATION INSTRUCTIONS Cont... Natural Gas Pressure Settings: The inlet supply or line pressure must be a minimum of 4.5” w.c. (1.
Northfire 42 11 INSTALLATION INSTRUCTIONS Cont... MOSPEED CONTROL 110F (43ºC) N.O. THERMAL SNAP SWITCH CONVECTION BLOWER LINE GROUND NEUTRAL SIDE OF
Northfire 42 12 INSTALLATION INSTRUCTIONS Cont... 42” 17 ½” 41” 29” 42” 58” FRAMING DIMENSIONS 42” 35 ¾” 17 ½” TERMINATION FRAMING 11” 10” NOTE: Be
Northfire 42 13 2468101214161820222426282468101212108642FT.VENTING CHARTVERTICAL HIEGHTHORIZONTAL LENGTHRestrictor 2No RestrictorRestrictor 1INSTALLA
Northfire 42 14 ALLOWABLE TERMINATION LOCATIONS Canadian Installations (1) US Installations (2) Canadian Installations (1) US Installations (2
Northfire 42 15 VENTING - RESTRICTOR PLACEMENT NOTE: Vent restrictors are designed to reduce vertical stack action for vent terminations which wi
Northfire 42 16 INSTALLATION INSTRUCTIONS Cont... For best venting performance, here are some general venting rules that we recommend: 1. Use only A
Northfire 42 17 Termination Fire-stop Sleeve 7” and 4” flex vent lengths (compressed Cement Screws Spring spacers 4” exhaust vent with spring spacers
Northfire 42 18 GLASS DOOR INSTALLATION INSTRUCTIONS Cont... WARNING: Do not attempt to remove the glass door when the appliance is hot. Removing t
Northfire 42 19 LOG PLACEMENT WARNING: Do not place logs in any other configuration than that shown. Under no circumstances are logs to be modified
Northfire 42 20 Locate the right log onto the locater pins as shown as shown Locate the rear top log onto the locater pin on the top of the rear log
Northfire 42 21 Locate the back left log on the locater pins Locate the left front log on the locater pins as shown
Northfire 42 22 Locate the center log on the locater pin on the burner and rest it on the rear log as shown Locate the right log onto the locater pin
Northfire 42 23 Place the coals on the burner making sure not to block any burner ports or air pas-sages. Do not place coals over the gap between th
Northfire 42 24 NOTE: Ensure that the fireplace is turned off and cool. 1 Remove the upper grilles by pulling the assembly forward. 2 Remove the l
Northfire 42 25 OPERATION INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTING INITIAL OPERATION • Check that the appliance is properly vented and con
Northfire 42 26 OPERATION INSTRUCTIONS Cont.. LIGHTING INSTRUCTIONS (copy of instruction plate found in control panel) 1. Set the thermostat to the l
Northfire 42 27 MAINTENANCE CAUTION : Do not conduct maintenance on the appliance while it is operating or while it is still hot. The exterior paint
Northfire 42 28 TROUBLESHOOTING SYMPTOM ACTION Pilot will not light after pressing the sparker many times. 1. When lighting the appliance for the fi
Northfire 42 29 TROUBLESHOOTING - Continued SYMPTOM ACTION The main burner does not turn on with the pilot lit. 3. Check to make sure the thermosta
CONTENTS Introduction 4 General Information 6 Appliance Description 7 Dimensions and Clearances 8 Installation Instructions 9 - 20 Operation Inst
Northfire 42 30 WIRING DIAGRAMS VALVE CONNECTIONS PILOT ASSEMBLY ON/OFF SWITCH OPTIONAL THERMOSTAT THERMOPILE SPARK ELECTRODE THERMOCOUPLE PILOT BURN
Northfire 42 31 SERVICING Before servicing, read the terms and conditions of the Archgard warranty at the back of the manual. Contact the Archgard au
Northfire 42 32 SERVICING • Open the lower grills. • The pressure test taps are located on the valve. Automatic valve: The taps are located in
Northfire 42 33 • Remove the gas component assembly, see above. • Mark all wires to be removed for proper reassembly. CAUTION: Wiring errors cause
Northfire 42 34 Parts can be ordered through your local dealer or distributor by giving ITEM # and DESCRIPTION. REPLACEMENT PARTS FOR THE NORTHFIRE 4
This Limited Warranty is made by ARCHGARD INDUSTRIES LTD., hereinafter referred to as “Archgard”. Archgard warrants to the original purchaser of an
POSTAGE FOLD DOWN AT LINE FOLD DOWN AT LINE & TAPE CLOSED CUT ALONG LINE CUT ALONG LINE CUT ALONG LINE WARRANTY REGISTRATION ARCHGARD INDUSTRIES
Archgard Industries Ltd. 7116 Beatty Drive Mission, B.C. V2V 6B4 Canada Website: www.archgard.com
Northfire 42 4 INTRODUCTION Congratulations on choosing an Archgard fireplace! The Northfire 42 is one of the most advanced direct vent fireplace he
Northfire 42 5 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall h
Northfire 42 6 GENERAL INFORMATION SPECIFICATIONS This appliance is tested and certified to the following US and Canadian gas appliance standards. -
Northfire 42 7 APPLIANCE DESCRIPTION Top Louvers (removable) Ceramic glass front Hinged bottom louvers for control access FLAT FRONT
Northfire 42 8 DIMENSIONS AND CLEARANCES APPLIANCE DIMENSIONS 3/8 ¾” SIDE VIEW FRONT VIEW TOP VIEW 44” 23 ¼” 6 ½” 4 ½” BACK 0” to stand-offs SIDES
Northfire 42 9 INSTALLATION INSTRUCTIONS PRECAUTIONS • This appliance must be installed by a qualified gas installer and the installation must confo